- WEMScontroller3 (see below).
- Run Channel Setup Wizard To Configure Analogue Outputs.
- Run Channel Setup Wizard To Configure Analogue Inputs.
- Run FanCoil Discover Wizard.
- Configure FanCoil Control Points.
- Assign A Schedule To The FanCoil.
The following steps define how to set up a FanCoil for the first time. If you would like to amend the settings of a FanCoil that has already been configured, see the FanCoil Configuration guide.
To set up a FanCoil for the first time, begin by discovering and configuring a WEMScontroller3, using the Auto Discover Wizard and Channel Setup Wizard. The WEMScontroller3 is ideally suited to controlling a FanCoil because of its 4 analogue outputs (3 of which are configurable) and 2 analogue inputs. One WEMScontroller3 is needed per FanCoil.
In addition to the steps above, the FanCoil setup requires that the system is able to measure the internal room space temperature. An existing temperature sensor can be used to provide this measurement.
The following process must be performed BEFORE attempting to use the FanCoil Discover Wizard.
WEMScontroller3
Begin by running the Auto Discover Wizard ( | ) and detecting the WEMScontroller3. For more detailed information on how to run this wizard, see the Auto Discover section.
- Click to begin the wizard.
- Press the WEMScontroller3 in order to discover the device. button on the
- The device will be discovered. Click to continue.
- The device will be configured by the wizard. Click to continue.
- Give the device a meaningful name, and then click to continue.
- Specify a location for the device, and then click to continue.
- Click Channel Setup Wizard. to begin the
Next Step
The WEMScontroller3 is now complete.
of theThe next step is to run the Channel Setup Wizard in order to Configure The Analogue Outputs.