- WEMScontroller3.
- Run Channel Setup Wizard To Configure Analogue Outputs.
- Run Channel Setup Wizard To Configure Analogue Inputs.
- Run AHU Discover Wizard.
- Configure AHU Control Points.
- Assign A Schedule To The AHU.
This guide covers the first-time setup of an AHU, and assumes that a WEMScontroller3 has already been discovered and had its analogue outputs and inputs set up.
With a suitably configured WEMScontroller3 in place, you can now discover and configure the AHU. Do the following:
- Go to | , and then click to begin the wizard.
- Enter a description for the AHU, and then click .
- Choose a location for the AHU, and then click .
- Choose the type of AHU (Re-circulation or Fresh Air), and then click .
- Click to the confirmation message.
- Click .
The AHU Discover Wizard is now complete and you will now be returned to the Floorplan.
If you do not see a new AHU icon in the Temperature Layer, exit and re-enter the user interface in order to refresh the display.
Next Step
The AHU Discover Wizard is now complete.
The next step is to Configure the AHU Control Points.