You are here: Using The System > FP AHU > First-time Setup (Modbus) > 2b. Control Points (FAU Only)

Configure FP AHU Control Points (Modbus FAU Only)

  1. Run FP AHU Discover Wizard.
  1. Click the new FP AHU icon, which will present the FP AHU Control Screen.

The Modbus FP AHU icon (magnified below) shows a red spot to indicate that the Object has not been configured. For more information on other icon statuses that are possible for FP AHUs, see FP AHU Icon Statuses.

WEMS

Floorplan showing an unconfigured FP AHU

Status Tab

The Control Screen will open in the Status tab. Information shown in green relates to data coming from the WEMS System; grey items relate to data coming from Modbus.

  1. Click the Edit Points button to configure the FP AHU.

Status tab

  1. Select options from the dropdown menus. In FAU only systems, the only settings that can be changed are those for space temperatures.

Choose up to 4 room temperature measures in the dropdowns to the middle right in order to set up temperature averaging for the space temperature. Although only a single room temperature measurement is necessary, the performance of the system is likely to improve if multiple measurements are averaged.

Status tab in editing mode

The fields shown in the Status tab are defined as follows.

Edit Points button Allows the user to define the necessary points for the FP AHU
Manual Override button This will disable the Heartbeat between the WEMS System and the unit meaning that unit will control to its own settings
WEMS AHU Status The current control status from the WEMS System
WEMS Ref Temp The current reference temperature that the WEMS System is controlling to
Heartbeat The status of the Modbus Heartbeat between the WEMS System and the AHU
Unit Status The current status from the AHU
Supply Air Current Supply Air Temp from the AHU
Space Temp Current Space Temp from the AHU
WEMS Space Temp Current Space Temp from the WEMS System. This can represent one temperature value or an average of up to 4 values

FP AHU Info Panel And Advanced Panel

The FP AHU Info Panel and Advanced Panel are used to manage the FP AHU setup. The Info Panel is found in the bottom-left corner. The Advanced Panel is accessed via the Advanced button at the bottom of the Info Panel (moderator password required). The Advanced Panel contains all of the settings available in the Info Panel plus some further settings.

FP AHU Info Panel (left) and Advanced Panel (right)

The settings of the Advanced Panel are as follows:

Description Description of the FP AHU Object
Asset Name Unique customer reference number for the FP AHU
AHU Enable Setpoint The FP AHU will enable when the reference temperature is above this setpoint
Hysteresis How many degrees the temperature has to drop below setpoint to disable the FP AHU
Heartbeat Enable or disable the Heartbeat setting If Heartbeat is enabled it will allow the WEMS System to communicate with the FP AHU via Modbus. Disabling the heartbeat will remove the Modbus link to the WEMS System and the unit will run to its own setpoints
Min Outside Air If the WEMS outside air temperature is below this setpoint then WEMS disable the DX Inhibit and the FP AHU controls to its own settings
Max Outside Air If the WEMS outside air temperature is above this setpoint then WEMS disable the DX Inhibit and the FP AHU controls to its own settings
Max Ref Temp If the WEMS reference temp temperature is above this then WEMS disable the DX Inhibit and the FP AHU controls to its own settings
AHU Stage Four pre-defined default AHU Enable Setpoints for the unit. Stage 1 has the lowest setpoints and Stage 4 has the highest

Settings Tab

  1. The values shown in the Settings tab are setpoints and parameters on the AHU. These can be changed via Modbus.

Settings tab

The fields shown in the Settings tab are defined as follows.

Temperature Setpoints
Free Cooling Above this setpoint the AHU will enable for Free Cooling
High Room Above this setpoint an alarm will be generated on the AHU that the room temperature is too high
Main Fan Speeds
Minimum The lowest % speed that the fan can run
Maximum The highest % speed that the fan can run
Miscellaneous
Filter Dirty Setpoint Above this setpoint a Filter Dirty alarm is generated on the AHU
Heartbeat Values
Period Number of seconds between each Modbus Heartbeat
Count If this number of heartbeats is missed then the Heartbeat is considered to be down

Stats Tab

  1. The Stats tab displays a read-only view of compressor and fan information.

Stats tab

The fields shown in the Stats tab are defined as follows.

Main Fan
Filter Pressure Current Filter Pressure of the Main Fan
Filter Condition Current Filter Condition of the Main Fan
Run Hours How long the Fan has been running since the last AHU reboot

Assets Tab

  1. The Assets tab displays a read-only view of additional information about the FP AHU.

Assets tab

The fields shown in the Assets tab are defined as follows.

AHU Manufacturer The manufacturer of the AHU
AHU Type The type of AHU (Fresh Air, DXFAU etc.)
Software The manufacturer software the unit is currently running
Filter Size The dimensions of the filter in millimetres and inches
Warranty End Date The warranty end date
  1. When all settings have been checked, click the 'X' button in the top-right corner to exit the Control Screen and return to the Floorplan.

WEMS User Guide version 4.0 20150130.
This guide relates to features up to and including 1.18.0.3