You are here: Products > Product Information > WMS-DIG-48V - Digital Input (48V)

WMS-DIG-48V - Digital Input (48V)

   

Product Description

This WEMS Digital Input module provides four optically isolated inputs for status and alarm monitoring or meter pulse counting. Maximum pulse count frequency is 10Hz. LEDs provide status indication for each channel. Inputs require (wetting) voltage of 12-48VDC.

For product operation and installation information please refer to the Digital Input (48V) user manual.

Features Pluggable, snap-fit modular system
Pluggable screw terminals
4 × Digital inputs: configurable for status, alarm or pulse meter
DIN rail mount
Status LEDs
Input voltage max. 48V DC
Compliance
EMC EN 301 489: Electromagnet compatibility
EN 61000: Electromagnet compatibility
Safety EN 60950: Information technology equipment
EN 60730: Automatic electrical controls
EN 50366: Domestic equipment

Specifications
Operating Temperature Range -10 to +50 DegC
Operating Humidity < 75% RH (Non-condensing)
Storage Temperature -20 to +85 DegC
Storage Humidity < 90% RH (Non-condensing)
Cooling Convection
Supply Voltage Modular BUS powered
Power 0.400W max
Digital Inputs (x4) Opto Isolated 48VDC digital inputs
Weight 64g (with 4-way connector)
Enclosure UL94-V0 flame retardant PC, IP20 rated
Mounting 35mm DIN rail (EN 50022, BS 5584, DIN 46277-3)

WEMS User Guide version 4.0 20150130.
This guide relates to features up to and including 1.18.0.3